Power QualityActive Harmonics Filter

NIPPEN AHF

  • • Stepless reactive power compensation
  • • Direct connection upto 800Vrms Grid supply
  • • 100% capacity for harmonic mitigation
  • • Response time <10ms
  • • Harmonic compensation up to 51st order to comply with IEEE 519 standard
  • • Enclosure IP rating upto IP55
  • • Ratings (A): 50,75,100,150A
  • • Industrial Plants
  • • Data Centers
  • • Steel, Cement, and Mining Industries
  • • Telecommunication Facilities
  • • Commercial Buildings

Technical Specifications

TECHNICAL SPECIFICATIONS


Input voltage AC

415V (304-456V)

Module Ratings (A)

50, 75, 100, 150A

Wiring System

3P-3W,3P-4W

Operating Frequency

50Hz/60Hz (-10% to +10%)

Current Transformer

100:5 to 10000:5

Harmonics Compensation

2-51st order

Harmonic Attenuation

>98%

HT Harmonic

Proprietary HV sensing technology for harmonic mitigation 

CT installation location 

Grid or Load side optional

Efficiency

>97.5%, Peak efficiency-98.5%

Inverter technology 

Three level topologies

Switching frequency

20kHz

Communication Protocol

RS485, Modbus, WiFi (remote control debugging and TCP/IP optional)

Full Response Time

<10ms, instant response<50us

Operating Temperature

-40⁰C to +50⁰C

Relative Humidity

<95%, No condensation

Size

500mm x 191mm x 582mm

Ingress Protection

Module IP20

Product Variants

RATINGS(AMPS)

DIMENSIONS

50A

500x 550x 130mm

75A

500x 550x 130mm

100A

500x 550x 130mm

150A

500x 550x 130mm

Let's discuss your requirements