Protection RelaysMotor Protection Relay

MPR-90

MPR-90
MPR-90
MPR-90
  • • Monitors Under/Over voltage,Under/Over Current,Under/Over frequency
  • • SPP,Short circuit,,Phase Loss/Sequence, Locked rotor,Phase assymetry.
  • • 3Ø-3 Wire / 4 Wire Selectable
  • • Programmable Tripping Parameter
  • • RS-485 Modbus Optional
  • • Fail Safe and Non Fail Safe Mode(selectable)
  • • 2 Relay Output
  • • Power Distribution Networks
  • • Residential Electrical Systems
  • • Distribution Panels
  • • LT / HT Panel
  • • Energy Management System
  • • DG Set Panels

Technical Specifications

INPUT SPECIFICATION

Network Connection

3Ø-3W ,3Ø-4W

Operating Voltage AC

160 to 280V AC L-N( for 3Ø-4W), 280 to 520V AC L-L (for 3Ø-3W)  

Frequency

45/65Hz

Accuracy

Class 1.0 (Standard)

DISPLAY AND KEY


Display

3 Row-4 Digit LED display

Key

SET UP/ ESC, UP, DOWN, ENTER/ALM RST

GENERAL SPECIFICATION 

Dimension(mm)

96X96mm

Panel Cutout

92X92mm

TRIP SETTINGS



Trip Setting

Under Voltage:  280 to 520V AC(L-L) (for 3Ø-3W) ,160 to 280V AC(L-N) (3Ø-4W)



Over Voltage

280 to 520V AC(L-L) (for 3Ø-3W) , 160 to 280V AC(L-N) 3Ø-4W)

Under Current


0.00 to CTR


Over Current

0.00 to CTR

Short Circut


1 - 9 Scale


Unbalance

0-100%

Lock Rotor Point

0.5 to 9.0 Scale

Over / Under Frequency

45.0 to 65.0 Hz

Phase Loss

yes

Phase sequence

yes




Time Parameter

Power ON Delay               : 0-999sec

Delay/Trip Time Delay      : 0-999sec 

Recovery Time Delay       : 0-999sec

Response Time                : <100ms

OUTPUT SPECIFICATION

Relay

2

Relay Type

1C/O (SPDT

Rating

NO5A@250V AC / NC3A@250V AC(res)

Operating Temp.

0 to 55°C

Relative Humidity

up to 95%RH

Product Variants



Let's discuss your requirements

Schedule consultation