Protection RelaysCurrent Protection Relay

600CPR

600CPR
600CPR
600CPR
  • • 1Ø-2W ,3Ø-4W
  • • Auxilliary Powered
  • • Monitors Under Current ,Over Current , Current Asymmetry
  • • Auto/Manual Reset
  • • Two Alarms output NO/NC
  • • Supply Voltage: 230V AC ± (10%) , 50 / 60Hz (Default)
  • • Power Distribution Networks
  • • Residential Electrical Systems
  • • Distribution Panels
  • • LT / HT Panel
  • • Energy Management System
  • • DG Set Panels

Technical Specifications

INPUT SPECIFICATION

Network connection

1Ø ,3Ø

Primary CT value

5A-999A(selectable)

Secondary Current AC

0.050-5A AC(6A max)

Resolution

0.01,0.1,1A,

Display and key

Display

1 Row 3 Digit LED Display

Key

SET UP/ESC, UP, ENTER/ALM RST

General specification 

Dimension(mm)

96X96mm

Panel Cutout

92X92mm

Output Specification

Relay

2

Relay Type

1C/O(SPDT)

Rating

NO/5A@250VAC, NC/3A @250VAC

Operating Temp.

0 to 55°C

Relative Humidity

95%RH

Auxiliary Supply Specifications

Supply Voltage

230V AC 50/60Hz, Auxiliary powered

Power Consumption (VA Rating)

20VA max

Trip Settings

Under Current

0-999A

Over Current

0-999A

Current Asymmetry

5.0-99.9%

Trip Time Settings

Power ON Delay

1-999sec

Trip Time Delay

0-999sec

Recovery Time Delay

0-999sec



Let's discuss your requirements